EvoSwitchJ.W. Lucasweg 35, 2031 BE Haarlem, The Netherlands+44 20 80 89 80 01 Показать на карте

General information

  • Address: J.W. Lucasweg 35, 2031 BE Haarlem, The Netherlands
  • Area: 40,000 sq.m. gross surface
  • Power capacity: 15 MW (expansion to 60 MW)
  • Quality level: Tier III
The EvoSwitch data center is one of the largest and most reliable data centers in Europe. The use of advanced premium infrastructure technologies guarantees customers a maximum uptime of 99.999% SLA. The data center is connected to Europe's largest AMS-IX and NL-IX traffic exchange points. The datacenter is a 3-storey purpose-built concrete and steel facility.

Facility details

Power supply system

  • Power capacity - 25 MW (expansion to 60 MW)
  • Generators: 25 Megawatts
  • Power redundancy options N+1 and 2N
  • 8 power transformers with 2500 kVA
  • 16 automatic DGUs x 1540 kVA (N+2)
  • 1.2 PUE (power usage effectiveness)
  • 48-hour fuel reserve
  • 99.99999% uptime since 2007

Cooling

  • Cooling system with 2N redundancy
  • Using freecooling
  • Hot and cold corridors
  • Temperature 24°C (± 5°C)
  • Relative humidity 50% (± 25%)

Fire Extinguishing

  • High-sensitivity smoke detection system VESDA (Very Early Smoke Detection System)
  • FirePro® / IG55 gas fire extinguishing system
  • Portable gas and foam extinguishers
  • Fire resistance of walls 1 hour

Security

  • On-Site Security Personnel 24/7
  • 3-meter-long electric fence across the perimeter of the data center building.
  • Guarded access to the territory, pass control
  • Complete monitoring of the entire territory of the facility with video cameras with motion sensors
  • Entrance to the guarded reception area via gateway booths equipped with ID card readers, access cards and biometric data (palm print scanning).
  • Entrance to the machine rooms is via access cards and biometric data reading (palm print and retina scanning).
  • Corridors, entrance doors and other critical infrastructure are controlled by the CCTV system.

Certificates

  • ISO 27001:2005 (Information Security Management System Certification (equivalent to NEN 7510))
  • ISO 9001:2008 (Quality Management System Certification)
  • ISAE3402 (SAS 70) (audit opinion on financial and internal control)
  • NEN 3140; 1010; 50110 (low voltage protection)
  • Borg Class 4 (construction and electronic network security)
  • AMS-IX Certified Data Center for AMS1
  • U.S. Green building council LEED Gold


FR590 Kleyerstraße, Frankfurt am Main, HE, 60326, Germany+44 20 80 89 80 01 Показать на карте

General information

  • Address: 90 Kleyerstraße, Frankfurt am Main, HE, 60326, Germany
  • Total space: Gross Area - 5,900 sq.m. Usable Area (White Space) - 3,190 sq.m.
  • UPS topology: – N + N

This is one of many state of the art IBX centers in key metropolitan areas throughout Europe that offer a full range of premium colocation, interconnection and support services to a wide range of secure digital ecosystems built by networks, enterprise, content, cloud and IT services companies and financial institutions.

Frankfurt FR5 IBX data center provides direct and settlement-free IP interconnection infrastructure in Germany for important banking, commerce, and telecommunications infrastructure.

Facility details

Power supply system

  • Total Provisioned UPS Power 1,620 kW
  • Electrical Distribution - Distributed Redundant
  • UPS Type Static UPS
  • UPS Redundancy N
  • Generator Redundancy N
  • Max Power Capacity Per Rack 3.0 kW

Cooling

  • Cooling capacity 3 MW
  • Cooling Redundancy N+1

Security

  • Security - 24x7
  • Biometric Authentication
  • Keycard Access
  • Dual Authentication
  • CCTV

For more information visit the official website.


General information

  • Area: 2 929 Sq m
  • Power capacity: 10,500 kVA (6.5 kW per rack)
  • Quality level: Tier-III
The Data Center facility is a freestanding brick building surrounded by a concrete fence. The total area of the territory is 1,735 ha.
There are two computer rooms in the main building with 289 and 269 sq.m. area for 148 and 133 rack space respectively.
Computer rooms are located in a special containment area ("house in the house") made of sandwich panels.

Facility details

Power supply system

  • Power supply with reservation according to the 2N scheme;
  • Uninterruptible power supplies - APC-MGE Galaxy 7000 (500 kVA), 4 UPS for each room;
  • Two rays supply power to each rack;
  • The power distribution in the rooms is made in cable ladder under the raised floor;
  • UPS battery capacity is designed to supply power to customer racks and data center information infrastructure within 6 minutes (time sufficient to start up diesel engines);
  • Electricity from the city is supplied by two cable inlets on two step-down transformers;

Guaranteed power supply is provided by four Wilson Diesel Generating units in container, with spare capacity of 1250 kVA, running on the bus bar, which provides a level of reserve of diesel generating units 3 + 1;
Oil and antifreeze of diesel engines are constantly heated, so that the diesel generating unit is always ready to start (start up time - less than 1 minute);
Fuel tanks of diesel generators are designed for 6 hours of operation. Prompt delivery of diesel fuel ensures the operation of data center even in the event of long-term failure of the city electric network; power supply will be provided to all engineering systems and offices of the data center.

Cooling

The cooling system is built on Hiref equipment. Precision two-circuit freon conditioners TADR1002 with upfeed air supply are installed in computer room. Chilled air from the air conditioners is supplied under the raised floor and further through the perforated tiles of the raised floor, is blown into the "cold" corridors between the racks. 

The air conditioners in the halls are reserved according to the N+1 scheme (one air conditioner per room is reserved). External condenser blocks (two for each conditioner) are placed on the site near the building.

External condensing units (two for each air conditioner) are placed on the site next to the building.

Fire extinguishing system

Computer rooms in the data center are protected by an automatic gas fire detection and extinguishing unit designed for early detection of a fire zone, issuing a fire signal and automatic extinguishing. Chladon 125, stored in modules of PGM type (gas fire extinguishing module), is used as fire extinguishing agent. 

The fire extinguishing method is volumetric, by means of filling the protected room with Chladon 125 vapors until the fire extinguishing concentration is obtained. To detect ignition in the protected premises smoke detectors are used, placed in the working space of the hall and under the raised floor. The unit is controlled by a fire safety device " РОСА-2SL".

Security

The complex security video surveillance devices include fixed color IP-camera internal and external performance, digital recorders, color video monitors. Upon customer request is possible to install additional cameras in the halls.
The contract with the Federal State Unitary Enterprise "Security" Russian Ministry of Internal Affairs ("Panic Button").

The data center's security tele- surveillance system provides:
  • On-Site Security Personnel 24/7
  • Round-the-clock video recording of areas on digital video recorders with indication of time, date, number of the video camera;
  • Displaying archived video images of areas on the automated working station of security posts by the commands of operators;
  • Priority display of video from surveillance cameras operating in alarm mode;
  • Automatic notification of the operator in case of system malfunction;
  • Automatic synchronization of date and time of closed-circuit television system equipment;
  • Storage of video archives from cameras - up to one month.

The complex of security tele surveillance devices includes stationary color IP-cameras, digital recording devices, color video monitors. At the customer's request it is possible to install additional video cameras in rooms. An agreement with the  FGUP "Security" of the Russian Ministry of Internal Affairs ("Alarm Button") has been concluded.



The data center on Korovinskoye Shosse is connected by fiber optic lines to the communication center on the MMTS-10 site (own cable 16 fibers) and the data center on Borovoi. There are two independent telecommunication inputs in the building. There are two independent telecommunication inputs in the building. The communication equipment is accommodated in open 19-inch racks located in computer rooms near the telecommunication input pits. If necessary, the channel bandwidth from the data center on Borovoi can be expanded by means of CWDM PacketLight sealing equipment (up to 80 Gbit/s), or by renting or purchasing additional optical fibers.

Cloud4Y has all the necessary licenses for providing communication services. 


General information

  • Address: Moscow, 8 Marta, 14 ul.
  • Area: 2 500 Sq m
  • Power capacity: 5 MW
  • Quality level: TIER III | TIER II
The M8 modular data center is one of the largest and technologically advanced data centers in Moscow. The datacenter is built in accordance with international standards and provides maximum reliability and security of clients' information systems.
The integrated control system allows for continuous monitoring and control of power supply, air conditioning, fire detection, access control and video surveillance system parameters.
All technological processes are supported and controlled on the basis of BMS Beckhoff. M8 data center provides a full range of data transfer and storage services, services for the arrangement of ICT-centers and backup DRC offices.
The M8 Data Center has an Internet traffic exchange point on its site and offers a wide range of international and Russian operators. It has a redundant fiber-optic network on independent routes to the main points of presence in Moscow, including the M9.This allows to guarantee customers uninterrupted operation of the network infrastructure in emergency situations and create distributed corporate networks and data storage systems.

Facility details

Power supply system

  • 4 entries from two independent power substations 2N redundancy scheme
  • Backup power supply system: UPS with 2N redundancy scheme, 9 diesel generators

Cooling

  • Two-circuit system using chillers, high precision air conditioners and free cooling
  • 2N and N+1 redundancy schemes

Fire extinguishing system

  • Automatic gas fire-extinguishing system Novec 1230

Security

  • CCTV system
  • Physical security with regular rounds 
  • Access control system based on electronic passes
  • Installation of additional customer security circuits

Certification

ISO 27001; ISO 9001; PCI DSS; certification for compliance with Federal Service for Technical and Export Control (FSTEC) requirements for personal data storage


«Linx»Saint-Petersburg, Repischeva str., 20A, lit. A+7 495 268–04–12 Показать на карте

General information


  • Address: Saint Petereburg, Rapicheva, 20A
  • Space: 9 000Sq m
  • Power Supply: 12 MW
  • Reliability: Complies with TIER III
Data Center "Na Repischeva" is one of the most technologically advanced data centers in St. Petersburg.
The data center was built in accordance with the requirements and guarantees of the reliability and security of customer information systems.

Data Center Description

Main power supply system

  • 2 entries from the gas power station
  • 1 city entry to the gas power station
  • N+1 redundancy scheme

Backup power supply system

  • UPS with 2N redundancy scheme
  • 3 Cummins diesel generators with N+1 redundancy scheme

Cooling system

  • Two-circuit system using chillers, high precision air conditioners and free cooling
  • 2N and N+1 redundancy schemes

Fire-extinguishing system

  • Automatic gas fire-extinguishing system FM 200

Security

  • 6 security circuits
  • CCTV system
  • Physical security with regular rounds
  • Access control system based on electronic passes and biometric data

Certification

Management & Operations Stamp of Approval, ISO 27001:2013, ISO 9001:2015, PCI DSS v3.2


TeknotelKozyatağı Mahallesi Saniye Ermutlu Sokak No:10 D:1-3 34742 Kadıköy İSTANBUL+7 495 603–72–71 Показать на карте

General information

  • Address:Kozyatağı Mahallesi Saniye Ermutlu Sokak No:10 D:1-3 34742 Kadıköy İSTANBUL
  • Area: 2,000 sq. meters
  • Total installed capacity: 5 MW
  • Backup power system
  • Reliability level: TIER III
The architecture, power supply, air conditioning and network systems of the data center are designed in accordance with the Tier 3+ standard. Physical and electronic security systems, systems for detecting and preventing floods and fires in the data center make it possible to ensure the uninterrupted operation of equipment located in the data center. System redundancy is built according to the 2N+1 scheme. This means that the system is completely duplicated, and there is one more spare element in addition. All energy resources used by the data center are 100% Renewable Energy certified, which emphasizes the environmental friendliness of the Turkish Cloud4Y data center. Also received ISO 27001, ISO 14001, ISO 9001 certificates.

Object description

Power supply system

  • Standby generators 2N+1
  • Uninterruptible power supplies 2N+1

Fire extinguishing system

  • Fire extinguishing system FM200

Certification

ISO 27001, ISO 14001, ISO 9001